Rinnai Infinity 24e - Storage

Meets the demand maintaining the temperature in a large storage vessel

Rinnai Infinity water heaters can be used as circulators to maintain the temperature in a large
storage vessels. This approach could be used where the hot water requirement exceeds the
flow capacity of manifold units, or where there is an intermittent large demand for hot water
in buildings such as hotels, hospitals, apartments etc.

         Storage Recovery Rates

           Storage Tank Capacity 300 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
1
52
1118
818
22
2
104
1936
1636
11
3
156
2745
2454
7

           Storage Tank Capacity 500 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
1
52
1318
818
36
2
104
2136
1636
18
3
156
2954
2454
12
4
208
3772
3272
9
5
260
4590
4090
7

           Storage Tank Capacity 800 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
2
104
2436
1636
29
3
156
3254
2454
19
4
208
4072
3272
14
5
260
4890
4090
11

Storage recovery rates for the 24e (based on a 44°C temperature rise)