Rinnai Infinity 26e - Storage

Meets the demand maintaining the temperature in a large storage vessel

Rinnai Infinity water heaters can be used as circulators to maintain the temperature in a large
storage vessels. This approach could be used where the hot water requirement exceeds the
flow capacity of manifold units, or where there is an intermittent large demand for hot water
in buildings such as hotels, hospitals, apartments etc.

         Storage Recovery Rates

           Storage Tank Capacity 300 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
1
54
1141
841
22
2
108
1982
1682
11
3
162
2823
2523
7

           Storage Tank Capacity 500 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
1
54
1341
841
36
2
108
2182
1682
18
3
162
3023
2523
12
4
216
3864
3364
9
5
270
4705
4205
7

           Storage Tank Capacity 800 Litres

  No.
   of
 units
    Maximum gas
     consumption
        (KW/hrs)
    1st hour
    recovery
      (1/h)
   2nd hour
   recovery
     (1/h)
 Approx
 recovery
  (mins)
2
108
2482
1682
29
3
162
3323
2523
19
4
216
4164
3364
14
5
270
5005
4025
11