Rinnai Infinity 32e - Storage
Meets the demand maintaining the temperature in a large storage vessel
Rinnai Infinity water heaters can be used as circulators to maintain the temperature in a large
storage vessels. This approach could be used where the hot water requirement exceeds the
flow capacity of manifold units, or where there is an intermittent large demand for hot water
in buildings such as hotels, hospitals, apartments etc.
Storage Recovery Rates
Storage Tank Capacity 300 Litres
No.
of
units
Maximum gas
consumption
(KW/hrs)
1st hour
recovery
(1/h)
2nd hour
recovery
(1/h)
Approx
recovery
(mins)
1
69
1371
1071
17
2
138
2442
2142
8
3
207
3513
3213
6
Storage Tank Capacity 500 Litres
No.
of
units
Maximum gas
consumption
(KW/hrs)
1st hour
recovery
(1/h)
2nd hour
recovery
(1/h)
Approx
recovery
(mins)
1
69
1571
1071
28
2
138
2642
2142
14
3
207
3713
3213
9
4
276
4748
4284
7
5
345
5855
5355
5
Storage Tank Capacity 800 Litres
No.
of
units
Maximum gas
consumption
(KW/hrs)
1st hour
recovery
(1/h)
2nd hour
recovery
(1/h)
Approx
recovery
(mins)
2
138
2942
2142
29
3
207
4013
3213
15
4
276
5084
4284
11
5
345
6155
5355
9
Storage recovery rates for the 32e (based on a 44°C temperature rise)